RGW1-24 series three pole outdoor disconnector with fuse-bases is the high voltage switch equipment, in the suitable for outdoor 24kV line internet with voltage and no load, to make separate and fabricate. With CS8 type manpower operate machinery to avoid earth line with power and composite flash-locks and wrong operate. The operator no need put another earth line. Pollution-proof type isolate switch of customer in filthy conduction area. It can solve the pollution of shed when it is work.
RGW-B 11-33kV
Type | Rated Voltage(kV) | Rated Current(A) | 4s Heat Steady Current(A) | Shock Steady Current(A) | Impulse Withstand Voltage(kV) | Power-Frequency Withstand Voltage(kV) |
RGW-B | 11 | 400 | 12500 | 31500 | 95 | 42 |
RGW-B | 33 | 600 | 12500 | 31500 | 195 | 80 |
12-15kV
Type |
Rated Voltage(kV) |
Rated Current(A) |
4s Heat Steady Current(A) |
Shock Steady Current(A) |
Impulse Withstand Voltage(kV) |
Power-Frequency Withstand Voltage(kV) |
||
To earth | Across the isolating distance | To earth | Across the isolating distance | |||||
GW9-12W/400 | 12 | 400 | 12500 | 31500 | 75 | 85 | 38 | 42 |
GW9-12W/630 | 12 | 630 | 12500 | 31500 | 75 | 85 | 38 | 42 |
GW9-12W/1250 | 12 | 1250 | 20000 | 50000 | 75 | 85 | 38 | 42 |
12-15kV
Type |
Rated Voltage(kV) |
Rated Current(A) |
Limit Passing Current(kA) |
10 sec Heat Stabilization Current(A) |
|
Reak Value | r.m.s | ||||
GW9-10 | 10,12,15 | 200 | 5 | 9 | 5 |
GW9-12 | 10,12,15 | 400 | 21 | 15 | 10 |
GW9-15 | 10,12,15 | 600 | 35 | 25 | 14 |
10,12,15 | 1000 | 50 | 35 | 20 |
12-15kV
Type |
Rated Voltage(kV) |
Rated Current(A) |
4s Heat Steady Current(A) |
Shock Steady Current(A) |
Impulse Withstand Voltage(kV) |
Power-Frequency Withstand Voltage(kV) |
||
To earth | Across the isolating distance | To earth | Across the isolating distance | |||||
HGW9-12W400 | 12-15 | 400 | 12500 | 31500 | 75 | 85 | 38 | 42 |
HGW9-12W630 | 12-15 | 630 | 12500 | 31500 | 75 | 85 | 38 | 42 |
500V
Type |
Rated Voltage(kV) |
Rated Current(A) |
Breaking Current(A) |
JDW2-500 | 500 | 500 | 30-500 |
JDW2-800 | 500 | 800 | 30-500 |
HGWR1/GWR1 0.5-1600V
Fuse Rated Current | 120A | 150A | 220A | 300A | 360A | 470A | 600A |
Fuse Specification | 0.15 | 0.20 | 0.30 | 0.50 | 0.60 | 0.80 | 0.90 |
Transformer Volume | 80 | 100 | 150 | 180-220 | 250 | 315-320 | 400 |