Guy Strain Insulator GY and BS Series

  Standard: BS 137, AS 3609   Voltage:0.4-33kV   Strain insulators are mainly used on the guy wire structure to balance the tension strength and also provide the insulating.
GUY STRAIN INSULATORS FOR LINES

BS-137

AS-3609

Type

11.1075

11.0522

11-3257G

GY-1

GY-2

GY-3

GY-4

Dimensions, mm A - Height

78

140

220

90

146

216

280

  B - Hole Centers Spacing

50

62

80

48

73

89

89

  C - Inner Diameter

37

60

120

40

44

67

67

  D - Outer Diameter

57

85

135

68

73

115

115

  E - Cable Hole Diameter

19

19

22

16

22

38

38

  F - Height To Hole

 

 

 

60

99

133

165

Mechanical Failing Load, kN

45

110

110

27

71

222

222

Low Frequency Flashover Voltage Dry, kV

30

35

23

/

/

/

/

  Wet, kV

15

18

48

10

15

20

30

Net Weight, Each, Approx. kg

1

1.4

4.8

0.7

1.25

3.8

5

 