Item No. |
Rated voltage kV |
Rated bending load kN |
Structure Height (mm) |
Min Arcing Distance (mm) |
Min Nominal Creepage Distance (mm) |
Lighting full- wave impulse withstand voltage (kV) |
Power Frequency Withstand Voltage (wet) |
Mounting Dimensions | |
Mounting Hole | Lower mounting hole | ||||||||
FZN4-12/4 |
12 |
4 |
230±3 |
125 |
330 |
75 |
75 |
M10 | 4×Φ14-Φ76 |
FZSW-12/4 |
12 |
4 |
235±3 |
125 |
330 |
75 |
75 |
2×M12-Φ76 | 4×M12-Φ76 |
FZSW-24/8 |
24 |
8 |
345±3 |
200 |
540 |
150 |
150 |
4×M12-Φ76 | 4×M12-Φ76 |
FZSW-24/8 |
24 |
8 |
345±3 |
200 |
540 |
150 |
150 |
4×Φ14-Φ140 | 4×Φ14-Φ140 |
FZSW-33/10 |
33 |
10 |
618±10 |
450 |
1080 |
220 |
220 |
4×Φ14-Φ140 | 4×Φ14-Φ140 |
FZSW-35/6-76 |
40.5 |
6 |
435±3 |
290 |
1260 |
185 |
185 |
2×M8-Φ36 | 4×Φ14-Φ76 |
FZSW-40.5/6L(IEC) |
40.5 |
6 |
435±3 |
340 |
1260 |
200 |
200 |
4×M12-Φ76 | 4×M12-Φ76 |
FZSW-72.5/8 |
72.5 |
8 |
780±5 |
600 |
1850 |
350 |
350 |
4×Φ14-Φ140 | 4×Φ14-Φ140 |
FZSW-72.5/10 |
72.5 |
10 |
780±5 |
600 |
1950 |
350 |
350 |
4×Φ14-Φ140 | 4×Φ14-Φ140 |
FZSW-126/8 |
126 |
8 |
1240±5 |
1050 |
3150 |
550 |
550 |
4×M12-Φ140 | 4×Φ18-Φ140 |
FZSW-126/10 |
126 |
10 |
1240±5 |
1050 |
3150 |
550 |
550 |
4×M12-Φ140 | 4×Φ14-Φ140 |
FZSW-126/12.5 |
126 |
12.5 |
1440±5 |
1050 |
3500 |
550 |
550 |
4×M12-Φ140 | 4×Φ14-Φ140 |
FZSW-252/6K |
252 |
6 |
2240±15 |
2070 |
6300 |
1050 |
1050 |
4×M16-Φ140 | 8×Φ20-Φ225 |
FZSW-252/8 |
252 |
8 |
2340±15 |
2000 |
6700 |
1050 |
1050 |
4×M16-Φ190 | 8×Φ20-Φ225 |