For medium/high voltage cable installations where “hot-working” is not permitted due to the presence of flammable gases in potentially explosive atmospheres cold shrink terminations can be supplied which do not require naked flame or heat source to install. Performance of 15KV
Test Requirement
Indoor moisture 11kV,300h,No flashover, no breakdown
Outdoor salt fog 11kV,1000h,No flashover, no breakdown
Partial discharge ≤10PC at 15kV
Heating cycles in air 22kV.Heating cycle at least 8h, 95℃-100℃ at least 2h, natural cooling at least 3h, total 60 heating cycles
AC voltage withstand 1min 35kV,No flashover, no breakdown
DC voltage withstand 15min 35kV,No flashover, no breakdown
AC voltage withstand 5min 35kV,No flashover, no breakdown
Impluse voltage (peak) 95kV,No flashover, no breakdown
Performance of 35KV
Test Requirement
Indoor moisture 32.5kV,300h,No flashover, no breakdown
Outdoor salt fog 32.5kV,1000h,No flashover, no breakdown
Partial discharge ≤10PC at 45kV
Heating cycles in air 65kV.Heating cycle at least 8h, 95℃-100℃ at least 2h, natural cooling at least 3h, total 60 heating cycles
AC voltage withstand 1min 104kV, No flashover, no breakdown
DC voltage withstand 15min 104kV, No flashover, no breakdown
AC voltage withstand 5min 117kV, No flashover, no breakdown
Impluse voltage (peak) 200kV,No flashover, no breakdown